JKLYJ — representative 1-core cable with matching cross section.
View Full-size Cross Section ↗

Overhead Cable

AL/XLPE 1kV Overhead Cable

Model / JKLYJ-LV

Rated Voltage
1kV
Materials
AL/XLPE
Custom Option Standards
  • BS 7870-5
Temperature

Max. conductor: ≤ 90 °C

Download Product Data ↓

Product Reference: xr-overhead-insulated-1kv-jklyj

Construction

Conductor Material
Aluminum
Conductor Form
Stranded
Insulation Material
XLPE
Load Bearing Neutral Options
Steel Strand, Aluminum Alloy Strand

Operating Conditions

Maximum Conductor Temperature

≤ 90 °C

Minimum Laying Temperature

≥ −20 °C

Short-circuit Temperature

≤ 250 °C · Maximum duration: 5 s

Bending & Motion

Minimum Bending Radius
D < 25 mm
≥ 4 D
D >= 25 mm
≥ 6 D

Applications

Applications

Overhead power transmission and distribution lines

Dimensions & Reference Values

Cores
1

Dimensions & mass

Cross section (mm²)Outside diameter (mm)Mass (kg/km)
10644
16769
25899
3510135
5011186
7012244
9515329
12016414
15018524
18520633
24023832
300251015
Cores
1

Electrical & mechanical values

Cross section (mm²)Insulation resistance 70 °C (MΩ·km)Insulation resistance 90 °C (MΩ·km)Max. resistance · 20 °C (Ω/km)Min. breaking force (N)
10≥ 0.0067≥ 0.673.081650
16≥ 0.0065≥ 0.651.912517
25≥ 0.0054≥ 0.541.23762
35≥ 0.0046≥ 0.460.8685177
50≥ 0.004≥ 0.40.6417011
70≥ 0.0039≥ 0.390.44310354
95≥ 0.0035≥ 0.350.3213727
120≥ 0.0035≥ 0.350.25317339
150≥ 0.0035≥ 0.350.20621033
185≥ 0.0035≥ 0.350.16426732
240≥ 0.0034≥ 0.340.12534679
300≥ 0.0033≥ 0.330.143349

Load-bearing neutral · Breaking force

Cross section (mm²)Steel · min. force (N)Aluminium alloy · min. force (N)
25300006284
35420008800
505655012569
708115017596
9511015023880
120—30164

Specification Ranges

Core & conductor combinations

Core configurationCross section (mm²)
1 core10–300
2 cores / 4 cores / 3+K10–120

Product Record

AL/XLPE 1kV Overhead Cable

Model: JKLYJ-LV
Reference: xr-overhead-insulated-1kv-jklyj

Catalogue Tags: overhead-cables

View the Public JSON Record

View the Standards Data