JKY — representative 2-core cable with matching cross section.
View Full-size Cross Section ↗

Overhead Cable

CU/PE 1kV Overhead Cable

Model / JKY-LV

Rated Voltage
1kV
Materials
CU/PE
Custom Option Standards
  • BS 7870-5
Temperature

Max. conductor: ≤ 70 °C

Download Product Data ↓

Product Reference: xr-overhead-insulated-1kv-jky

Construction

Conductor Material
Copper
Conductor Form
Stranded
Insulation Material
PE
Load Bearing Neutral Options
Steel Strand, Aluminum Alloy Strand

Operating Conditions

Maximum Conductor Temperature

≤ 70 °C

Minimum Laying Temperature

≥ −20 °C

Short-circuit Temperature

≤ 150 °C · Maximum duration: 5 s

Bending & Motion

Minimum Bending Radius
D < 25 mm
≥ 4 D
D >= 25 mm
≥ 6 D

Applications

Applications

Overhead power transmission and distribution lines

Dimensions & Reference Values

Cores
1

Dimensions & reference values

Cross section (mm²)Insulation resistance 70 °C (MΩ·km)Insulation resistance 90 °C (MΩ·km)Max. resistance · 20 °C (Ω/km)Min. breaking force (N)Outside diameter (mm)
10≥ 0.0067≥ 0.671.90634716
16≥ 0.0065≥ 0.651.19854867
25≥ 0.0054≥ 0.540.74984658
35≥ 0.0046≥ 0.460.541173110
50≥ 0.004≥ 0.40.3991650211
70≥ 0.0039≥ 0.390.2762346112
95≥ 0.0035≥ 0.350.1993175915
120≥ 0.0035≥ 0.350.1583991116
150≥ 0.0035≥ 0.350.1284950518
185≥ 0.0035≥ 0.350.10216184620
240≥ 0.0034≥ 0.340.07777982323
300≥ 0.0033≥ 0.33—9978825

Load-bearing neutral · Breaking force

Cross section (mm²)Steel · min. force (N)Aluminium alloy · min. force (N)
25300006284
35420008800
505655012569
708115017596
9511015023880
120—30164

Specification Ranges

Core & conductor combinations

Core configurationCross section (mm²)
1 core10–300
2 cores / 4 cores / 3+K10–120

Product Record

CU/PE 1kV Overhead Cable

Model: JKY-LV
Reference: xr-overhead-insulated-1kv-jky

Catalogue Tags: overhead-cables

View the Public JSON Record

View the Standards Data