JKLYJ — representative 3-core cable with matching cross section.
View Full-size Cross Section ↗

Overhead Cable

AL/XLPE 10kV Overhead Cable

Model / JKLYJ-MV

Rated Voltage
10kV
Materials
AL/XLPE
Custom Option Standards
  • BS EN 50397-1
Temperature

Max. conductor: ≤ 90 °C

Download Product Data ↓

Product Reference: xr-overhead-insulated-10kv-jklyj

Construction

Conductor Material
Aluminum
Conductor Form
Stranded
Insulation Material
XLPE

Operating Conditions

Maximum Conductor Temperature

≤ 90 °C

Minimum Laying Temperature

≥ −20 °C

Short-circuit Temperature

≤ 250 °C · Maximum duration: 5 s

Bending & Motion

Minimum Bending Radius
1 core
20 * (D + d) mm · Tolerance: 5%
Multicore
15 * (D + d) mm · Tolerance: 5%

Applications

Applications

Overhead power transmission and distribution lines

Dimensions & Reference Values

Cores
1

Dimensions & reference values

Cross section (mm²)Insulation resistance 70 °C (MΩ·km)Insulation resistance 90 °C (MΩ·km)Max. resistance · 20 °C (Ω/km)Mass (kg/km)Min. breaking force (N)
10≥ 0.0067≥ 0.673.08138—
16≥ 0.0065≥ 0.651.91168—
25≥ 0.0054≥ 0.541.22183762
35≥ 0.0046≥ 0.460.8682565177
50≥ 0.004≥ 0.40.6413217011
70≥ 0.0039≥ 0.390.44345010354
95≥ 0.0035≥ 0.350.3249413727
120≥ 0.0035≥ 0.350.25357717339
150≥ 0.0035≥ 0.350.20669121033
185≥ 0.0035≥ 0.350.16480326732
240≥ 0.0034≥ 0.340.12599734679
300≥ 0.0033≥ 0.330.1116843349

Load-bearing neutral · Breaking force

Cross section (mm²)Steel · min. force (N)Aluminium alloy · min. force (N)
25300006284
35420008800
505655012569
708115017596
9511015023880
120—30164

Construction & Material Notes

Construction Details
Conductor Compacted
Yes

Specification Ranges

Core & conductor combinations

Core configurationCross section (mm²)
1 core / 3 cores / 3+K10–300

Product Record

AL/XLPE 10kV Overhead Cable

Model: JKLYJ-MV
Reference: xr-overhead-insulated-10kv-jklyj

Catalogue Tags: overhead-cables · medium-voltage

View the Public JSON Record