JKLHYJ — representative 1-core cable with matching cross section.
View Full-size Cross Section ↗

Overhead Cable

AL Alloy/XLPE 10kV Overhead Cable

Model / JKLHYJ

Rated Voltage
10kV
Materials
AL Alloy/XLPE
Custom Option Standards
  • BS EN 50397-1
Temperature

Max. conductor: ≤ 90 °C

Download Product Data ↓

Product Reference: xr-overhead-insulated-10kv-jklhyj

Construction

Conductor Material
Aluminum Alloy
Conductor Form
Stranded
Insulation Material
XLPE

Operating Conditions

Maximum Conductor Temperature

≤ 90 °C

Minimum Laying Temperature

≥ −20 °C

Short-circuit Temperature

≤ 250 °C · Maximum duration: 5 s

Bending & Motion

Minimum Bending Radius
1 core
20 * (D + d) mm · Tolerance: 5%
Multicore
15 * (D + d) mm · Tolerance: 5%

Applications

Applications

Overhead power transmission and distribution lines

Dimensions & Reference Values

Cores
1

Dimensions & reference values

Cross section (mm²)Insulation resistance 70 °C (MΩ·km)Insulation resistance 90 °C (MΩ·km)
10≥ 0.0067≥ 0.67
16≥ 0.0065≥ 0.65
25≥ 0.0054≥ 0.54
35≥ 0.0046≥ 0.46
50≥ 0.004≥ 0.4
70≥ 0.0039≥ 0.39
95≥ 0.0035≥ 0.35
120≥ 0.0035≥ 0.35
150≥ 0.0035≥ 0.35
185≥ 0.0035≥ 0.35
240≥ 0.0034≥ 0.34
300≥ 0.0033≥ 0.33

Load-bearing neutral · Breaking force

Cross section (mm²)Steel · min. force (N)Aluminium alloy · min. force (N)
25300006284
35420008800
505655012569
708115017596
9511015023880
120—30164

Construction & Material Notes

Construction Details
Conductor Compacted
Yes

Specification Ranges

Core & conductor combinations

Core configurationCross section (mm²)
1 core / 3 cores / 3+K10–300

Product Record

AL Alloy/XLPE 10kV Overhead Cable

Model: JKLHYJ
Reference: xr-overhead-insulated-10kv-jklhyj

Catalogue Tags: overhead-cables · medium-voltage

View the Public JSON Record

View the Standards Data