N-YJV — representative 3-core cable with matching cross section.
View Full-size Cross Section ↗

Power Cable

CU/XLPE/PVC 3.6/6kV - 26/35kV Flame-retardant Fire-resistant Screened Power Cable

Model / N-YJV-MV

Rated Voltage
3.6/6kV - 26/35kV
Materials
CU/XLPE/PVC
Standards
  • IEC 60502-2
  • IEC 60502-4 — Cable Accessory Tests
  • EN IEC 60332-3-22 — Fire Test · Category A
View all 7 standardsShow fewer
  • EN IEC 60332-3-23 — Fire Test · Category B
  • EN IEC 60332-3-24 — Fire Test · Category C
  • IEC 60754-1 — Halogen Acid Gas Test
  • IEC 60754-2 — Acidity & Conductivity Test
Features
Flame-retardant / Fire-resistant / Screened
Temperature

Max. conductor: ≤ 90 °C

Download Product Data ↓

Product Reference: xr-mv-fire-resistant-n_yjv

Construction

Conductor Material
Copper
Conductor Form
Stranded
Insulation Material
XLPE
Each core Conductor Screen
Yes
Each core Insulation Screen
Yes
Each core Metal Screen
Yes
Outer Sheath Material
PVC
Fire Barrier
Yes
Oxygen Barrier
Yes

Features

Flame Retardant
Yes
Fire Resistant
Yes

Operating Conditions

Maximum Conductor Temperature

≤ 90 °C

Short-circuit Temperature

≤ 250 °C · Maximum duration: 5 s

Bending & Motion

Minimum Bending Radius · Fixed

15 to 20 D

Electrical & Test Requirements

Fire Test Requirement
Test Temperature
950 °C
Duration
90 min

Applications

Applications
  • Medium-voltage circuits requiring continued supply during fire
  • Hospitals, schools, metro systems and high-rise buildings

Specification Ranges

Core & conductor combinations

Core configurationCross section (mm²)Rated voltage
125 · 35 · 50 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 500 · 6303.6/6kV · 6/6kV · 6/10kV · 8.7/10kV · 8.7/15kV
135 · 50 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 500 · 63012/20kV
150 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 500 · 63018/30kV · 21/35kV · 26/35kV
325 · 35 · 50 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 5003.6/6kV · 6/6kV · 6/10kV · 8.7/10kV · 8.7/15kV
335 · 50 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 50012/20kV
350 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 50018/30kV · 21/35kV · 26/35kV
3508.7/15kV
Core count
1–3
Cross section (mm²)
25–630

Product Record

CU/XLPE/PVC 3.6/6kV - 26/35kV Flame-retardant Fire-resistant Screened Power Cable

Model: N-YJV-MV
Reference: xr-mv-fire-resistant-n_yjv

Catalogue Tags: power-cables · medium-voltage · fire-resistant · flame-retardant · screened

View the Public JSON Record

View the Standards Data