Construction
- Conductor Material
- Copper
- Conductor Form
- Stranded
- Insulation Material
- Mica Tape
- Metal Sheath Material
- Copper
- Outer Sheath Material
- Polyolefin
Features
+
- Flame Retardant
- Yes
- Fire Resistant
- Yes
- Low Smoke Halogen Free
- Yes
Operating Conditions
+
- Maximum Conductor Temperature
≤ 90 °C
Bending & Motion
+
- Minimum Bending Radius
- D < 7 mm
- ≥ 2 D
- 7 <= D < 12 mm
- ≥ 3 D
- 12 <= D < 15 mm
- ≥ 4 D
- D >= 15 mm
- ≥ 6 D
Electrical & Test Requirements
+
- Insulation Resistance
- Cable length > 100 m
- ≥ 100 MΩ·km
- Cable length < 100 m
- ≥ 1,000 MΩ
- Voltage Test Requirement
- Voltage Test Requirement
- 3,500 V AC · Duration: 300 s
- Frequency
- Power frequency
Construction & Material Notes
+
- Construction Notes
- Mica-based inorganic mineral insulation
- Inorganic composite fire-resistant wrapping
- Continuously welded corrugated Copper sheath
- Manufacturing Description
Flexible construction permits continuous manufacture, delivery on drums and conventional cable-laying methods.
- Conductor Copper Purity
- Value
- 99.99 %
- Material
- oxygen free Copper
- Construction Details
- Metal Sheath Form
- Corrugated
- Insulation Component
- Mica Tape
Applications
+
- Applications
- Power distribution, lighting and fire-safety circuits
- High-rise and public buildings, hospitals and schools
- Industrial installations requiring fire-resistant circuits
Installation & Ordering
+
- Installation
- Do not twist, knot or drag the cable across abrasive surfaces.
- Fix at bends and on both sides of intermediate joints.
- Separate single-core circuits by at least twice the cable diameter; closer spacing requires current-rating derating.
- Use an outer protective sheath in corrosive environments and for buried or conduit installation.
- Single-core Fixing
Do not use ferromagnetic material such as iron wire to tie or fix single-core cables.
- Maximum Fixing Spacing
- D < 9 mm · Horizontal Spacing
- ≤ 600 mm
- D < 9 mm · Vertical Spacing
- ≤ 800 mm
- 9 <= D < 15 mm · Horizontal Spacing
- ≤ 900 mm
- 9 <= D < 15 mm · Vertical Spacing
- ≤ 1,200 mm
- D >= 15 mm · Horizontal Spacing
- ≤ 1,500 mm
- D >= 15 mm · Vertical Spacing
- ≤ 2,000 mm
- Terminations
- Seal cut ends promptly against moisture if the cable will not be terminated immediately.
- Follow the manufacturer's termination and jointing procedure.
- Keep metallic sheath swarf out of the insulation and recheck insulation resistance during termination.
- Continuous Length Capability
- Maximum
- 2000 m
- Expansion & Vibration Bends
- Minimum Radius (D)
- 6
- Shapes
- S · omega
- Natural Meander Allowance
- Maximum Excursion (D)
- 2
- Maximum Is Exclusive
- Yes
- Ferromagnetic Conduit
- Individual Single Core In Ferromagnetic Conduit Permitted
- No
Specification Ranges
Core & conductor combinations
Product Record
CU/Mica Tape/Polyolefin 0.6/1kV LSZH Flame-retardant Fire-resistant Power Cable
Model: WD-YTTW
Reference: xr-mineral-copper-sheath-flexible-0.6-1-wd_yttw
Catalogue Tags: mineral-insulated · power-cables · fire-resistant · flame-retardant · lszh
View the Public JSON Record↗View the Standards Data↗