Power Cable
CU/PVC/PVC 0.6/1kV Power Cable
Model / VV
0.6/1kVView Details →

Power Cable
Model / ZB-VLV22
Max. conductor: ≤ 70 °C
Product Reference: xr-lv-pvc-power-0.6-1-zb_vlv22
Product Details
≤ 70 °C
−15 to 70 °C
≥ 0 °C
≤ 160 °C · Maximum duration: 5 s
50 Hz AC
Power transmission and distribution; fixed installation in the environments described for the selected construction.
| Cross section (mm²) | Air 40 °C Flat Current (A) | Air 40 °C Trefoil Current (A) | Soil 25 °C Flat Current (A) | Soil 25 °C Trefoil Current (A) |
|---|---|---|---|---|
| 2.5 | 26 | 23 | 28 | 25 |
| 4 | 34 | 30 | 36 | 32 |
| 6 | 45 | 40 | 47 | 41 |
| 10 | 59 | 52 | 60 | 54 |
| 16 | 78 | 69 | 77 | 68 |
| 25 | 102 | 90 | 98 | 86 |
| 35 | 123 | 108 | 116 | 103 |
| 50 | 150 | 132 | 140 | 123 |
| 70 | 187 | 165 | 172 | 152 |
| 95 | 230 | 203 | 205 | 180 |
| 120 | 268 | 236 | 233 | 205 |
| 150 | 311 | 274 | 265 | 234 |
| 185 | 358 | 316 | 298 | 262 |
| 240 | 422 | 372 | 349 | 308 |
| 300 | 486 | 429 | 395 | 349 |
| 400 | 578 | 509 | 456 | 402 |
| 500 | 674 | 595 | 521 | 459 |
| 630 | 791 | 698 | 560 | 529 |
| Cross section (mm²) | Air 40 °C Current (A) | Soil 25 °C Current (A) |
|---|---|---|
| 2.5 | 17 | 23 |
| 4 | 23 | 31 |
| 6 | 31 | 40 |
| 10 | 41 | 51 |
| 16 | 55 | 66 |
| 25 | 70 | 85 |
| 35 | 87 | 102 |
| 50 | 106 | 122 |
| 70 | 135 | 153 |
| 95 | 164 | 189 |
| 120 | 194 | 209 |
| 150 | 223 | 235 |
| 185 | 252 | 265 |
| 240 | 305 | 306 |
| 300 | 346 | 347 |
| 400 | — | — |
| 500 | — | — |
| 630 | — | — |
| Core configuration | Cross section (mm²) |
|---|---|
| 2 cores / 3 cores | 2.5–500 |
| 4 cores / 3+1 core | 2.5–500 |
| 5 cores / 3+2 cores / 4+1 core | 50–500 |
AL/PVC/PVC 0.6/1kV Flame-retardant B Steel Tape Armored Power Cable
Model: ZB-VLV22
Reference: xr-lv-pvc-power-0.6-1-zb_vlv22
Catalogue Tags: power-cables · low-voltage · flame-retardant · armored