Bare Conductor
AL Bare Conductor
Model / JL
Voltage Not ProvidedView Details →

Product Reference: xr-bare-conductors-jlha1
Product Details
Overhead electrical power lines
| Nominal section (mm²) | Outside diameter (mm) | Mass (kg/km) |
|---|---|---|
| 10 | 4.05 | 27.4 |
| 16 | 5.13 | 44 |
| 25 | 6.39 | 68.2 |
| 35 | 7.56 | 95.5 |
| 50 | 9.06 | 137.2 |
| 70 | 10.7 | 191.7 |
| 95 | 12.5 | 261.5 |
| 150 | 15.9 | 412.2 |
| 210 | 18.8 | 576.8 |
| 240 | 20.1 | 661.1 |
| 300 | 22.5 | 825 |
| 400 | 26 | 1102 |
| 500 | 29.1 | 1380.9 |
| 630 | 32.7 | 1741.8 |
| Nominal section (mm²) | Calculated section (mm²) | Wire count | Wire diameter (mm) |
|---|---|---|---|
| 10 | 10.02 | 7 | 1.35 |
| 16 | 16.08 | 7 | 1.71 |
| 25 | 24.94 | 7 | 2.13 |
| 35 | 34.91 | 7 | 2.52 |
| 50 | 50.14 | 7 | 3.02 |
| 70 | 70.07 | 7 | 3.57 |
| 95 | 95.14 | 7 | 4.16 |
| 150 | 149.96 | 19 | 3.17 |
| 210 | 209.85 | 19 | 3.75 |
| 240 | 239.96 | 19 | 4.01 |
| 300 | 299.43 | 37 | 3.21 |
| 400 | 399.98 | 37 | 3.71 |
| 500 | 500.48 | 37 | 4.15 |
| 630 | 631.3 | 61 | 3.63 |
| Nominal section (mm²) | Breaking force (kN) | Resistance · 20 °C (Ω/km) |
|---|---|---|
| 10 | 3.26 | 3.3205 |
| 16 | 5.22 | 2.0695 |
| 25 | 8.11 | 1.3339 |
| 35 | 11.35 | 0.9529 |
| 50 | 16.3 | 0.6635 |
| 70 | 22.07 | 0.4748 |
| 95 | 29.97 | 0.3514 |
| 150 | 48.74 | 0.2229 |
| 210 | 66.1 | 0.1593 |
| 240 | 75.59 | 0.1397 |
| 300 | 97.32 | 0.1119 |
| 400 | 125.99 | 0.0838 |
| 500 | 157.65 | 0.0671 |
| 630 | 198.86 | 0.0532 |
AL Alloy Bare Conductor
Model: JLHA1
Reference: xr-bare-conductors-jlha1
Catalogue Tags: bare-conductors · overhead-conductors
View the Public JSON Record