JL — bare conductor with matching strand section.
View Full-size Cross Section ↗

Bare Conductor

AL Bare Conductor

Model / JL

Rated Voltage
Not provided in the public record
Materials
AL
Custom Option Standards
  • IEC 61089
Download Product Data ↓

Product Reference: xr-bare-conductors-jl

Construction

Conductor Material
Aluminum
Conductor Form
Stranded

Applications

Applications

Overhead electrical power lines

Installation & Ordering

Delivery Conditions
Length Tolerance (%)
0.5
Maximum Short Length Share (%)
5
Minimum Short Length Fraction
1/3

Dimensions & Reference Values

Dimensions & mass

Nominal section (mm²)Min. length (m)Outside diameter (mm)Mass (kg/km)
3540007.594
5040009135.3
70300010.8194.9
95200012.5260.2
120150014.3333.2
150100015.8407
185150017.5502.4
210125018.8576.8
240100020656.3
300100022.4819.8
500100029.11385.5

Conductor construction

Nominal section (mm²)Calculated section (mm²)Wire countWire diameter (mm)
3534.3672.5
5049.4873
7071.2573.6
9595.1474.16
120121.21192.85
150148.07193.15
185182.8193.5
210209.85193.75
240238.76194
300297.57373.2
500502.9374.16

Electrical & mechanical values

Nominal section (mm²)Breaking force (kN)Resistance · 20 °C (Ω/km)
356.010.8333
508.410.5787
7011.40.4019
9515.220.301
12020.610.2374
15024.430.1943
18530.160.1574
21033.580.1371
24038.20.1205
30049.10.0969
50080.460.0573

Specification Ranges

Listed cross sections (mm²)
35 · 50 · 70 · 95 · 120 · 150 · 185 · 210 · 240 · 300 · 500

Product Record

AL Bare Conductor

Model: JL
Reference: xr-bare-conductors-jl

Catalogue Tags: bare-conductors · overhead-conductors

View the Public JSON Record

View the Standards Data