Bare Conductor
CU Bare Conductor
Model / TJ
Voltage Not ProvidedView Details →

Product Reference: xr-bare-conductors-jl
Product Details
Overhead electrical power lines
| Nominal section (mm²) | Min. length (m) | Outside diameter (mm) | Mass (kg/km) |
|---|---|---|---|
| 35 | 4000 | 7.5 | 94 |
| 50 | 4000 | 9 | 135.3 |
| 70 | 3000 | 10.8 | 194.9 |
| 95 | 2000 | 12.5 | 260.2 |
| 120 | 1500 | 14.3 | 333.2 |
| 150 | 1000 | 15.8 | 407 |
| 185 | 1500 | 17.5 | 502.4 |
| 210 | 1250 | 18.8 | 576.8 |
| 240 | 1000 | 20 | 656.3 |
| 300 | 1000 | 22.4 | 819.8 |
| 500 | 1000 | 29.1 | 1385.5 |
| Nominal section (mm²) | Calculated section (mm²) | Wire count | Wire diameter (mm) |
|---|---|---|---|
| 35 | 34.36 | 7 | 2.5 |
| 50 | 49.48 | 7 | 3 |
| 70 | 71.25 | 7 | 3.6 |
| 95 | 95.14 | 7 | 4.16 |
| 120 | 121.21 | 19 | 2.85 |
| 150 | 148.07 | 19 | 3.15 |
| 185 | 182.8 | 19 | 3.5 |
| 210 | 209.85 | 19 | 3.75 |
| 240 | 238.76 | 19 | 4 |
| 300 | 297.57 | 37 | 3.2 |
| 500 | 502.9 | 37 | 4.16 |
| Nominal section (mm²) | Breaking force (kN) | Resistance · 20 °C (Ω/km) |
|---|---|---|
| 35 | 6.01 | 0.8333 |
| 50 | 8.41 | 0.5787 |
| 70 | 11.4 | 0.4019 |
| 95 | 15.22 | 0.301 |
| 120 | 20.61 | 0.2374 |
| 150 | 24.43 | 0.1943 |
| 185 | 30.16 | 0.1574 |
| 210 | 33.58 | 0.1371 |
| 240 | 38.2 | 0.1205 |
| 300 | 49.1 | 0.0969 |
| 500 | 80.46 | 0.0573 |
AL Bare Conductor
Model: JL
Reference: xr-bare-conductors-jl
Catalogue Tags: bare-conductors · overhead-conductors
View the Public JSON Record