  "product_id": "xr-bare-conductors-jl",
  "family_id": "bare-conductors",
  "model": "JL",
  "source_notation": "JL",
  "specification_ranges": [
    {
      "profile_id": "source-parameter-table",
      "range_type": "source_table_exact_or_conditioned_combination",
      "cross_section_mm2": {
        "values": [
          35,
          50,
          70,
          95,
          120,
          150,
          185,
          210,
          240,
          300,
          500
        ]
      },
      "constraint_note": "Listed nominal cross-sections from the partial specification table; not a continuous range or an exhaustive manufacturing capability."
    }
  ],
  "construction": {
    "conductor_material": "aluminum",
    "insulation_material": "none",
    "outer_sheath_material": "none",
    "screen": {
      "present": false,
      "type": "none"
    },
    "armor": {
      "present": false,
      "type": "none"
    },
    "conductor_form": "stranded"
  },
  "functions": {},
  "cross_section_examples": [
    {
      "example_id": "bare-single-conductor",
      "basis": "manual_model_table",
      "scope": "declared_component_structure",
      "not_to_scale": true,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "assembly",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": []
        },
        {
          "node_id": "conductor",
          "parent_id": "assembly",
          "kind": "core",
          "count": 1,
          "layers": [
            {
              "kind": "conductor",
              "strand_groups": [
                {
                  "material": "aluminum",
                  "wire_count": 7
                }
              ],
              "material": "aluminum",
              "form": "stranded"
            }
          ]
        }
      ],
      "illustrated_counts": {
        "cores": 1,
        "groups": 0,
        "tubes": 0,
        "reinforcements": 0
      },
      "note": "One bare electrical conductor, not multiple insulated cable cores. Steel or alloy core strands are contained inside the outer conductor strands. No insulation or jacket is added."
    }
  ],
  "technical_details": {
    "applications": {
      "basis": "declared",
      "values": [
        "Overhead electrical power lines"
      ]
    },
    "delivery_conditions": {
      "basis": "declared",
      "length_tolerance_percent": 0.5,
      "maximum_short_length_share_percent": 5,
      "minimum_short_length_fraction": "1/3",
      "conditions": "The printed length tolerance is plus or minus 5 per mille (0.5%). Short lengths are at least one third of the manufacturing length; other lengths may be agreed."
    },
    "dimensional_table": {
      "basis": "declared",
      "reported_row_count": 11,
      "rows": [
        {
          "source_row_id": "JL-35",
          "nominal_cross_section_mm2": 35,
          "calculated_cross_section_mm2": 34.36,
          "wire_count": 7,
          "wire_diameter_mm": 2.5,
          "minimum_manufacturing_length_m": 4000,
          "outer_diameter_mm": 7.5,
          "mass_kg_per_km": 94,
          "calculated_breaking_force_kN": 6.01,
          "dc_resistance_at_20c_ohm_per_km": 0.8333
        },
        {
          "source_row_id": "JL-50",
          "nominal_cross_section_mm2": 50,
          "calculated_cross_section_mm2": 49.48,
          "wire_count": 7,
          "wire_diameter_mm": 3,
          "minimum_manufacturing_length_m": 4000,
          "outer_diameter_mm": 9,
          "mass_kg_per_km": 135.3,
          "calculated_breaking_force_kN": 8.41,
          "dc_resistance_at_20c_ohm_per_km": 0.5787
        },
        {
          "source_row_id": "JL-70",
          "nominal_cross_section_mm2": 70,
          "calculated_cross_section_mm2": 71.25,
          "wire_count": 7,
          "wire_diameter_mm": 3.6,
          "minimum_manufacturing_length_m": 3000,
          "outer_diameter_mm": 10.8,
          "mass_kg_per_km": 194.9,
          "calculated_breaking_force_kN": 11.4,
          "dc_resistance_at_20c_ohm_per_km": 0.4019
        },
        {
          "source_row_id": "JL-95",
          "nominal_cross_section_mm2": 95,
          "calculated_cross_section_mm2": 95.14,
          "wire_count": 7,
          "wire_diameter_mm": 4.16,
          "minimum_manufacturing_length_m": 2000,
          "outer_diameter_mm": 12.5,
          "mass_kg_per_km": 260.2,
          "calculated_breaking_force_kN": 15.22,
          "dc_resistance_at_20c_ohm_per_km": 0.301
        },
        {
          "source_row_id": "JL-120",
          "nominal_cross_section_mm2": 120,
          "calculated_cross_section_mm2": 121.21,
          "wire_count": 19,
          "wire_diameter_mm": 2.85,
          "minimum_manufacturing_length_m": 1500,
          "outer_diameter_mm": 14.3,
          "mass_kg_per_km": 333.2,
          "calculated_breaking_force_kN": 20.61,
          "dc_resistance_at_20c_ohm_per_km": 0.2374
        },
        {
          "source_row_id": "JL-150",
          "nominal_cross_section_mm2": 150,
          "calculated_cross_section_mm2": 148.07,
          "wire_count": 19,
          "wire_diameter_mm": 3.15,
          "minimum_manufacturing_length_m": 1000,
          "outer_diameter_mm": 15.8,
          "mass_kg_per_km": 407,
          "calculated_breaking_force_kN": 24.43,
          "dc_resistance_at_20c_ohm_per_km": 0.1943
        },
        {
          "source_row_id": "JL-185",
          "nominal_cross_section_mm2": 185,
          "calculated_cross_section_mm2": 182.8,
          "wire_count": 19,
          "wire_diameter_mm": 3.5,
          "minimum_manufacturing_length_m": 1500,
          "outer_diameter_mm": 17.5,
          "mass_kg_per_km": 502.4,
          "calculated_breaking_force_kN": 30.16,
          "dc_resistance_at_20c_ohm_per_km": 0.1574
        },
        {
          "source_row_id": "JL-210",
          "nominal_cross_section_mm2": 210,
          "calculated_cross_section_mm2": 209.85,
          "wire_count": 19,
          "wire_diameter_mm": 3.75,
          "minimum_manufacturing_length_m": 1250,
          "outer_diameter_mm": 18.8,
          "mass_kg_per_km": 576.8,
          "calculated_breaking_force_kN": 33.58,
          "dc_resistance_at_20c_ohm_per_km": 0.1371
        },
        {
          "source_row_id": "JL-240",
          "nominal_cross_section_mm2": 240,
          "calculated_cross_section_mm2": 238.76,
          "wire_count": 19,
          "wire_diameter_mm": 4,
          "minimum_manufacturing_length_m": 1000,
          "outer_diameter_mm": 20,
          "mass_kg_per_km": 656.3,
          "calculated_breaking_force_kN": 38.2,
          "dc_resistance_at_20c_ohm_per_km": 0.1205
        },
        {
          "source_row_id": "JL-300",
          "nominal_cross_section_mm2": 300,
          "calculated_cross_section_mm2": 297.57,
          "wire_count": 37,
          "wire_diameter_mm": 3.2,
          "minimum_manufacturing_length_m": 1000,
          "outer_diameter_mm": 22.4,
          "mass_kg_per_km": 819.8,
          "calculated_breaking_force_kN": 49.1,
          "dc_resistance_at_20c_ohm_per_km": 0.0969
        },
        {
          "source_row_id": "JL-500",
          "nominal_cross_section_mm2": 500,
          "calculated_cross_section_mm2": 502.9,
          "wire_count": 37,
          "wire_diameter_mm": 4.16,
          "minimum_manufacturing_length_m": 1000,
          "outer_diameter_mm": 29.1,
          "mass_kg_per_km": 1385.5,
          "calculated_breaking_force_kN": 80.46,
          "dc_resistance_at_20c_ohm_per_km": 0.0573
        }
      ],
      "scope": "Original model-specific calculated reference values. No interpolation, substitute model or arbitrary combination is created."
    }
  },
  "category_ids": [
    "bare-conductors",
    "overhead-conductors"
  ],
  "english_name": "AL Bare Conductor",
  "english_name_modules": [
    {
      "type": "materials",
      "value": "AL"
    },
    {
      "type": "product_type",
      "value": "Bare Conductor"
    }
  ],
  "display_identity": {
    "voltage_class": null,
    "qualifiers": [],
    "suffix_origin": "none",
    "notes": [
      "No website suffix is added; the display model preserves the source model."
    ],
    "model_label": "JL",
    "title": "JL — Bare Conductor",
    "enquiry_reference": {
      "source_model": "JL",
      "product_id": "xr-bare-conductors-jl",
      "rated_voltage": null,
      "instruction": "Quote the source model and product_id, together with the required rated voltage, core configuration and cross-section. Website suffixes are reference labels, not manufacturer ordering codes."
    }
  }
}