Construction
- Conductor Material
- Copper
- Conductor Form
- Stranded
- Insulation Material
- XLPE
- Each core Conductor Screen
- Yes
- Each core Insulation Screen
- Yes
- Each core Metal Screen
- Yes
- Outer Sheath Material
- Polyolefin
- Oxygen Barrier
- Yes
Features
+
- Flame Retardant
- Yes
- Flame Retardant Class
- B1
- Low Smoke Halogen Free
- Yes
Operating Conditions
+
- Maximum Conductor Temperature
≤ 90 °C
- Ambient Temperature
−15 to 90 °C
- Minimum Laying Temperature
≥ 0 °C
- Short-circuit Temperature
≤ 250 °C · Maximum duration: 5 s
Bending & Motion
+
- Minimum Bending Radius
- 1 core
- ≥ 20 D
- Multicore
- ≥ 15 D
- Minimum Bending Radius · At Joints
- 1 core
- ≥ 15 D
- Multicore
- ≥ 12 D
Electrical & Test Requirements
+
- Reaction-to-fire Requirements
- Classification
- B1
- Test Standard
- GB 31247
- Flame spread
- ≤ 1.5 m
- Peak heat release rate
- ≤ 30 kW
- Total heat release
- ≤ 15 MJ · Duration: 1,200 s
- Fire growth rate index
- ≤ 150 W/s
- Peak smoke production rate
- ≤ 0.25 m²/s
- Total smoke production
- ≤ 50 m² · Duration: 1,200 s
- Vertical flame spread
- ≤ 425 mm
Construction & Material Notes
+
- Conductor Material
- Copper Purity (%)
- 99.99
- Material Grade
- oxygen free Copper
Applications
+
- Applications
- Metro stations and transport hubs
- Airports
- Hospitals
- High-rise buildings
- Shopping centres, hotels and exhibition centres
Installation & Ordering
+
- Handling
- Keep drums upright and secure during lifting, transport and storage.
- Inspect for damage and check insulation resistance before installation.
- Provide allowance for vibration, thermal expansion and building movement.
- Installation
- Avoid twisting, knotting and dragging across sharp or abrasive surfaces.
- Fix the cable at bends and on both sides of joints.
- Do not use ferromagnetic ties or clamps around single-core cables.
- Provide mechanical protection where damage may occur.
- Natural Snaking Amplitude
- Less Than (× Outside Diameter): 2
- Single Core Circuit Separation
- Minimum (× Outside Diameter): 2 · Closer Spacing Requires Ampacity Derating: Yes
- Single Core Fixings Must Be Nonmagnetic
- Yes
- Natural Snaking Amplitude
- Less Than (× Outside Diameter): 2
- Single Core Circuit Separation
- Minimum (× Outside Diameter): 2 · Closer Spacing Requires Ampacity Derating: Yes
- Single Core Fixings Must Be Nonmagnetic
- Yes
- Movement Allowance Bends
- Shapes
- S · omega
- Minimum Radius (× Outside Diameter)
- 15
Specification Ranges
Core & conductor combinations
Product Record
CU/XLPE/Polyolefin 8.7/15kV LSZH Flame-retardant B1 Screened Power Cable
Model: WDZB1-YJY-MV
Reference: xr-b1-power-8.7-15-wdzb1_yjy
Catalogue Tags: power-cables · medium-voltage · flame-retardant · b1 · lszh · screened
View the Public JSON Record↗View the Standards Data↗