WDZB2-YJY63 — representative 1-core cable with matching cross section.
View Full-size Cross Section ↗

Power Cable

CU/XLPE/Polyolefin 0.6/1kV LSZH Flame-retardant B2 Non-magnetic Tape Armored Power Cable

Model / WDZB2-YJY63

Rated Voltage
0.6/1kV
Materials
CU/XLPE/Polyolefin
Custom Option Standards
  • IEC 60502-1
Features
LSZH / Flame-retardant B2 / Non-magnetic Tape Armored
Temperature

Max. conductor: ≤ 90 °C

Download Product Data ↓

Product Reference: xr-b2-power-0.6-1-wdzb2_yjy63

Construction

Conductor Material
Copper
Conductor Form
Stranded
Insulation Material
XLPE
Armor
Non Magnetic Tape
Outer Sheath Material
Polyolefin

Features

Flame Retardant
Yes
Flame Retardant Class
B2
Low Smoke Halogen Free
Yes

Operating Conditions

Maximum Conductor Temperature

≤ 90 °C

Ambient Temperature

−15 to 90 °C

Minimum Laying Temperature

≥ 0 °C

Short-circuit Temperature

≤ 250 °C · Maximum duration: 5 s

Bending & Motion

Minimum Bending Radius
1 core
≥ 15 D
Multicore
≥ 12 D
Minimum Bending Radius · At Joints
1 core
≥ 12 D
Multicore
≥ 10 D

Electrical & Test Requirements

Reaction-to-fire Requirements
Classification
B2
Test Standard
GB 31247
Flame spread
≤ 2.5 m
Peak heat release rate
≤ 60 kW
Total heat release
≤ 30 MJ · Duration: 1,200 s
Fire growth rate index
≤ 300 W/s
Peak smoke production rate
≤ 1.5 m²/s
Total smoke production
≤ 400 m² · Duration: 1,200 s
Vertical flame spread
≤ 425 mm

Applications

Applications

Low-voltage power distribution

Installation & Ordering

Handling
  • Keep drums upright and secure during lifting, transport and storage.
  • Inspect for damage and check insulation resistance before installation.
  • Provide allowance for vibration, thermal expansion and building movement.
Installation
  • Avoid twisting, knotting and dragging across sharp or abrasive surfaces.
  • Fix the cable at bends and on both sides of joints.
  • Do not use ferromagnetic ties or clamps around single-core cables.
  • Provide mechanical protection where damage may occur.
Natural Snaking Amplitude
Less Than (× Outside Diameter): 2
Single Core Circuit Separation
Minimum (× Outside Diameter): 2 · Closer Spacing Requires Ampacity Derating: Yes
Single Core Fixings Must Be Nonmagnetic
Yes

Fixing-point spacing

Cable diameter D (mm)Horizontal max. (mm)Vertical max. (mm)
D < 9600800
9 ≤ D < 159001200
D ≥ 1515002000
Natural Snaking Amplitude
Less Than (× Outside Diameter): 2
Single Core Circuit Separation
Minimum (× Outside Diameter): 2 · Closer Spacing Requires Ampacity Derating: Yes
Single Core Fixings Must Be Nonmagnetic
Yes

Support span

Cable diameter D (mm)Horizontal max. (mm)Vertical max. (mm)
D ≤ 204001500
D > 208001000
Movement Allowance Bends
Shapes
S · omega
Minimum Radius (× Outside Diameter)
15

Dimensions & Reference Values

Cores
1

Dimensions & reference values

Core configurationOutside diameter (mm)Mass (kg/km)Reference current (A)
1 core · 1.5 mm²12.9258.0218
1 core · 2.5 mm²13.3279.331
1 core · 4 mm²13.7305.240
1 core · 6 mm²14.2339.152
1 core · 10 mm²15.5417.570
1 core · 16 mm²16.5502.892
1 core · 25 mm²18.2641.3120
1 core · 35 mm²19752.7145
1 core · 50 mm²20.3908.5175
1 core · 70 mm²22.31156.1225
1 core · 95 mm²241448280
1 core · 120 mm²25.91729.5330
1 core · 150 mm²27.52045.4380
1 core · 185 mm²29.52453.6442
1 core · 240 mm²32.23051.4527
1 core · 300 mm²34.63661.7610
1 core · 400 mm²38.14620.8708
1 core · 500 mm²43.16099.1820
1 core · 630 mm²47.67610.1940

Specification Ranges

Core & conductor combinations

Core configurationCross section (mm²)Section limits (mm²)
1 core1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 · 150 · 185 · 240 · 300 · 400 · 500 · 6301.5–630

Product Record

CU/XLPE/Polyolefin 0.6/1kV LSZH Flame-retardant B2 Non-magnetic Tape Armored Power Cable

Model: WDZB2-YJY63
Reference: xr-b2-power-0.6-1-wdzb2_yjy63

Catalogue Tags: power-cables · low-voltage · flame-retardant · b2 · lszh · armored

View the Public JSON Record

View the Standards Data