  "product_id": "xr-pvc-control-450-750-zc_kvvp",
  "family_id": "pvc-control-450-750",
  "model": "ZC-KVVP",
  "source_notation": "ZA(B,C)-KVVP",
  "rated_voltage": "450/750V",
  "specification_ranges": [
    {
      "profile_id": "control-table-1",
      "range_type": "source_table_exact_or_conditioned_combination",
      "core_count": {
        "min": 2,
        "max": 61,
        "recommended_values": [
          2,
          3,
          4,
          5,
          6,
          7,
          8,
          10,
          12,
          14,
          16,
          19,
          24,
          27,
          30,
          37,
          44,
          52,
          61
        ]
      },
      "cross_section_mm2": {
        "values": [
          6,
          4,
          1,
          2.5
        ]
      },
      "constraint_note": "Manual-declared combination, transcribed in the printed column order. Only the listed cross-sections belong to this core-count interval; recommended counts are not an exhaustive enumeration."
    },
    {
      "profile_id": "control-table-2",
      "range_type": "source_table_exact_or_conditioned_combination",
      "core_count": {
        "min": 2,
        "max": 14,
        "recommended_values": [
          2,
          3,
          4,
          5,
          6,
          7,
          8,
          10,
          12,
          14
        ]
      },
      "cross_section_mm2": {
        "values": [
          1.5,
          0.75
        ]
      },
      "constraint_note": "Manual-declared combination, transcribed in the printed column order. Only the listed cross-sections belong to this core-count interval; recommended counts are not an exhaustive enumeration."
    },
    {
      "profile_id": "control-table-3",
      "range_type": "source_table_exact_or_conditioned_combination",
      "core_count": {
        "min": 2,
        "max": 10,
        "recommended_values": [
          2,
          3,
          4,
          5,
          6,
          7,
          8,
          10
        ]
      },
      "cross_section_mm2": {
        "values": [
          10
        ]
      },
      "constraint_note": "Manual-declared combination, transcribed in the printed column order. Only the listed cross-sections belong to this core-count interval; recommended counts are not an exhaustive enumeration."
    },
    {
      "profile_id": "section-range",
      "cross_section_mm2": {
        "min": 0.5,
        "max": 10
      },
      "range_type": "declared_selectable_range",
      "constraint_note": "Section range only; core configurations and individual combinations are not established by this response."
    },
    {
      "profile_id": "core-count-range",
      "core_count": {
        "min": 2,
        "max": 61
      },
      "range_type": "declared_selectable_range",
      "constraint_note": "Core-count range only; use separately documented combinations. This range does not authorize every cross-section at every core count."
    }
  ],
  "construction": {
    "conductor_material": "copper",
    "insulation_material": "pvc",
    "outer_sheath_material": "pvc",
    "screen": {
      "present": true,
      "type": "copper_wire_braid",
      "scope": "overall"
    },
    "armor": {
      "present": false,
      "type": "none"
    },
    "conductor_form": "stranded"
  },
  "functions": {
    "flame_retardant": true,
    "flame_retardant_class": [
      "C"
    ],
    "low_smoke_halogen_free": false
  },
  "cross_section_examples": [
    {
      "example_id": "control-nineteen-core-diagram",
      "basis": "manual_model_table_and_diagram",
      "scope": "model_table_structure_applied_to_illustrated_configuration",
      "not_to_scale": true,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "cable",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": [
            {
              "kind": "bedding"
            },
            {
              "kind": "metal_screen",
              "material": "copper_wire_braid"
            },
            {
              "kind": "outer_sheath",
              "material": "pvc"
            }
          ]
        },
        {
          "node_id": "cores",
          "parent_id": "cable",
          "kind": "core",
          "count": 19,
          "layers": [
            {
              "kind": "conductor",
              "material": "copper",
              "form": "stranded"
            },
            {
              "kind": "insulation",
              "material": "pvc"
            }
          ]
        }
      ],
      "illustrated_counts": {
        "cores": 19,
        "groups": 0,
        "tubes": 0,
        "reinforcements": 0
      },
      "note": "Nineteen cores are read from the shared construction drawing. The model-specific screen and armour are taken from the adjacent model table; this does not declare nineteen cores at every selectable section."
    }
  ],
  "technical_details": {
    "applications": {
      "basis": "declared",
      "values": [
        "Control, monitoring and protection circuits",
        "Connections between instruments and automation equipment"
      ]
    },
    "system_frequency": {
      "basis": "declared",
      "unit": "Hz",
      "value": 50,
      "supply": "AC"
    },
    "minimum_laying_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": 0
    },
    "maximum_conductor_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 70,
      "conditions": "Continuous operation"
    },
    "minimum_bending_radius_fixed": {
      "basis": "declared",
      "unit": "D",
      "conditions": "Fixed installation; D is the actual overall cable diameter.",
      "diameter_definition": "D is the actual overall cable diameter.",
      "min": 12
    }
  },
  "category_ids": [
    "control-cables",
    "flame-retardant",
    "screened"
  ],
  "english_name": "CU/PVC/PVC 450/750V Flame-retardant C Screened Control Cable",
  "english_name_modules": [
    {
      "type": "materials",
      "value": "CU/PVC/PVC"
    },
    {
      "type": "rated_voltage",
      "value": "450/750V"
    },
    {
      "type": "features",
      "value": "Flame-retardant C Screened"
    },
    {
      "type": "product_type",
      "value": "Control Cable"
    }
  ],
  "display_identity": {
    "voltage_class": null,
    "qualifiers": [],
    "suffix_origin": "none",
    "notes": [
      "No website suffix is added; the display model preserves the source model."
    ],
    "model_label": "ZC-KVVP",
    "title": "ZC-KVVP — Control Cable",
    "enquiry_reference": {
      "source_model": "ZC-KVVP",
      "product_id": "xr-pvc-control-450-750-zc_kvvp",
      "rated_voltage": "450/750V",
      "instruction": "Quote the source model and product_id, together with the required rated voltage, core configuration and cross-section. Website suffixes are reference labels, not manufacturer ordering codes."
    }
  }
}