  "product_id": "xr-overhead-insulated-1kv-jklv",
  "family_id": "overhead-insulated-1kv",
  "model": "JKLV",
  "source_notation": "JKLV",
  "rated_voltage": "1kV",
  "specification_ranges": [
    {
      "profile_id": "single",
      "core_configurations": [
        "1 core"
      ],
      "cross_section_mm2": {
        "min": 10,
        "max": 300
      },
      "range_type": "declared_continuous_range_not_expanded"
    },
    {
      "profile_id": "multi",
      "core_configurations": [
        "2 cores",
        "4 cores",
        "3+K"
      ],
      "cross_section_mm2": {
        "min": 10,
        "max": 120
      },
      "range_type": "declared_continuous_range_not_expanded"
    }
  ],
  "construction": {
    "conductor_material": "aluminum",
    "insulation_material": "pvc",
    "outer_sheath_material": "none",
    "screen": {
      "present": false,
      "type": "none"
    },
    "armor": {
      "present": false,
      "type": "none"
    },
    "conductor_form": "stranded",
    "load_bearing_neutral_options": [
      "steel_strand",
      "aluminum_alloy_strand"
    ]
  },
  "functions": {
    "low_smoke_halogen_free": false
  },
  "cross_section_examples": [
    {
      "example_id": "overhead-single-core",
      "basis": "manual_diagram",
      "scope": "model_diagram",
      "not_to_scale": true,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "cable",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": []
        },
        {
          "node_id": "cores",
          "parent_id": "cable",
          "kind": "core",
          "count": 1,
          "layers": [
            {
              "kind": "conductor",
              "material": "aluminum",
              "form": "stranded"
            },
            {
              "kind": "insulation",
              "material": "pvc"
            }
          ]
        }
      ],
      "illustrated_counts": {
        "cores": 1,
        "groups": 0,
        "tubes": 0,
        "reinforcements": 0
      }
    },
    {
      "example_id": "overhead-three-plus-neutral",
      "basis": "manual_diagram",
      "scope": "model_diagram",
      "not_to_scale": true,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "cable",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": [
            {
              "kind": "group_boundary",
              "physical_layer": false
            }
          ]
        },
        {
          "node_id": "cores",
          "parent_id": "cable",
          "kind": "core",
          "count": 3,
          "layers": [
            {
              "kind": "conductor",
              "material": "aluminum",
              "form": "stranded"
            },
            {
              "kind": "insulation",
              "material": "pvc"
            }
          ]
        },
        {
          "node_id": "load-bearing-neutral",
          "parent_id": "cable",
          "kind": "reinforcement",
          "count": 1,
          "layers": [],
          "role": "load_bearing_neutral",
          "material_options": [
            "steel",
            "aluminum_alloy"
          ]
        }
      ],
      "illustrated_counts": {
        "cores": 3,
        "groups": 0,
        "tubes": 0,
        "reinforcements": 1
      },
      "note": "Three insulated phase cores and one uninsulated load-bearing neutral. The neutral material is an ordering option, not a default; there is no common outer sheath."
    }
  ],
  "technical_details": {
    "applications": {
      "basis": "declared",
      "values": [
        "Overhead power transmission and distribution lines"
      ]
    },
    "minimum_laying_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": -20
    },
    "minimum_bending_radius": {
      "basis": "declared",
      "cases": [
        {
          "conditions": "D < 25 mm",
          "min": 4,
          "unit": "D"
        },
        {
          "conditions": "D >= 25 mm",
          "min": 6,
          "unit": "D"
        }
      ],
      "diameter_definition": "D is the actual overall cable diameter."
    },
    "maximum_conductor_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 70,
      "conditions": "Continuous operation"
    },
    "short_circuit_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 160,
      "maximum_duration_s": 5
    },
    "dimensional_table": {
      "basis": "declared",
      "reported_row_count": 12,
      "rows": [
        {
          "source_row_id": "10",
          "core_count": 1,
          "cross_section_mm2": 10,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0067
            },
            {
              "test_temperature_c": 90,
              "min": 0.67
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 3.08,
          "minimum_conductor_breaking_force_N": 1650,
          "outer_diameter_mm": 6,
          "mass_kg_per_km": 53
        },
        {
          "source_row_id": "16",
          "core_count": 1,
          "cross_section_mm2": 16,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0065
            },
            {
              "test_temperature_c": 90,
              "min": 0.65
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 1.91,
          "minimum_conductor_breaking_force_N": 2517,
          "outer_diameter_mm": 7,
          "mass_kg_per_km": 82
        },
        {
          "source_row_id": "25",
          "core_count": 1,
          "cross_section_mm2": 25,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0054
            },
            {
              "test_temperature_c": 90,
              "min": 0.54
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 1.2,
          "minimum_conductor_breaking_force_N": 3762,
          "outer_diameter_mm": 8,
          "mass_kg_per_km": 115
        },
        {
          "source_row_id": "35",
          "core_count": 1,
          "cross_section_mm2": 35,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0046
            },
            {
              "test_temperature_c": 90,
              "min": 0.46
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.868,
          "minimum_conductor_breaking_force_N": 5177,
          "outer_diameter_mm": 10,
          "mass_kg_per_km": 157
        },
        {
          "source_row_id": "50",
          "core_count": 1,
          "cross_section_mm2": 50,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.004
            },
            {
              "test_temperature_c": 90,
              "min": 0.4
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.641,
          "minimum_conductor_breaking_force_N": 7011,
          "outer_diameter_mm": 11,
          "mass_kg_per_km": 211
        },
        {
          "source_row_id": "70",
          "core_count": 1,
          "cross_section_mm2": 70,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0039
            },
            {
              "test_temperature_c": 90,
              "min": 0.39
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.443,
          "minimum_conductor_breaking_force_N": 10354,
          "outer_diameter_mm": 12,
          "mass_kg_per_km": 273
        },
        {
          "source_row_id": "95",
          "core_count": 1,
          "cross_section_mm2": 95,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0035
            },
            {
              "test_temperature_c": 90,
              "min": 0.35
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.32,
          "minimum_conductor_breaking_force_N": 13727,
          "outer_diameter_mm": 15,
          "mass_kg_per_km": 369
        },
        {
          "source_row_id": "120",
          "core_count": 1,
          "cross_section_mm2": 120,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0035
            },
            {
              "test_temperature_c": 90,
              "min": 0.35
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.253,
          "minimum_conductor_breaking_force_N": 17339,
          "outer_diameter_mm": 16,
          "mass_kg_per_km": 459
        },
        {
          "source_row_id": "150",
          "core_count": 1,
          "cross_section_mm2": 150,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0035
            },
            {
              "test_temperature_c": 90,
              "min": 0.35
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.206,
          "minimum_conductor_breaking_force_N": 21033,
          "outer_diameter_mm": 18,
          "mass_kg_per_km": 580
        },
        {
          "source_row_id": "185",
          "core_count": 1,
          "cross_section_mm2": 185,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0035
            },
            {
              "test_temperature_c": 90,
              "min": 0.35
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.164,
          "minimum_conductor_breaking_force_N": 26732,
          "outer_diameter_mm": 20,
          "mass_kg_per_km": 703
        },
        {
          "source_row_id": "240",
          "core_count": 1,
          "cross_section_mm2": 240,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0034
            },
            {
              "test_temperature_c": 90,
              "min": 0.34
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.125,
          "minimum_conductor_breaking_force_N": 34679,
          "outer_diameter_mm": 23,
          "mass_kg_per_km": 919
        },
        {
          "source_row_id": "300",
          "core_count": 1,
          "cross_section_mm2": 300,
          "insulation_resistance_MOhm_km": [
            {
              "test_temperature_c": 70,
              "min": 0.0033
            },
            {
              "test_temperature_c": 90,
              "min": 0.33
            }
          ],
          "maximum_conductor_resistance_20c_ohm_per_km": 0.1,
          "minimum_conductor_breaking_force_N": 43349,
          "outer_diameter_mm": 25,
          "mass_kg_per_km": 1122
        }
      ],
      "scope": "Model/material-specific columns from the original single-conductor table. No mass or electrical value is borrowed from a different conductor alloy. Printed temperature columns are preserved as source reference values."
    },
    "load_bearing_neutral_breaking_force": {
      "basis": "declared",
      "rows": [
        {
          "cross_section_mm2": 25,
          "steel_minimum_N": 30000,
          "aluminum_alloy_minimum_N": 6284
        },
        {
          "cross_section_mm2": 35,
          "steel_minimum_N": 42000,
          "aluminum_alloy_minimum_N": 8800
        },
        {
          "cross_section_mm2": 50,
          "steel_minimum_N": 56550,
          "aluminum_alloy_minimum_N": 12569
        },
        {
          "cross_section_mm2": 70,
          "steel_minimum_N": 81150,
          "aluminum_alloy_minimum_N": 17596
        },
        {
          "cross_section_mm2": 95,
          "steel_minimum_N": 110150,
          "aluminum_alloy_minimum_N": 23880
        },
        {
          "cross_section_mm2": 120,
          "aluminum_alloy_minimum_N": 30164
        }
      ],
      "conditions": "Only for the separately selected load-bearing neutral; these are not the phase-conductor breaking forces."
    }
  },
  "category_ids": [
    "overhead-cables"
  ],
  "english_name": "AL/PVC 1kV Overhead Cable",
  "english_name_modules": [
    {
      "type": "materials",
      "value": "AL/PVC"
    },
    {
      "type": "rated_voltage",
      "value": "1kV"
    },
    {
      "type": "product_type",
      "value": "Overhead Cable"
    }
  ],
  "display_identity": {
    "voltage_class": "LV",
    "qualifiers": [],
    "suffix_origin": "none",
    "notes": [
      "No website suffix is added; the display model preserves the source model."
    ],
    "model_label": "JKLV",
    "title": "JKLV — Overhead Cable",
    "enquiry_reference": {
      "source_model": "JKLV",
      "product_id": "xr-overhead-insulated-1kv-jklv",
      "rated_voltage": "1kV",
      "instruction": "Quote the source model and product_id, together with the required rated voltage, core configuration and cross-section. Website suffixes are reference labels, not manufacturer ordering codes."
    }
  }
}