  "product_id": "xr-lv-pvc-power-0.6-1-zb_vv22",
  "family_id": "lv-pvc-power-0.6-1",
  "model": "ZB-VV22",
  "source_notation": "ZA(B,C)-VV22",
  "rated_voltage": "0.6/1kV",
  "specification_ranges": [
    {
      "profile_id": "2-or-3-core",
      "core_configurations": [
        "2 cores",
        "3 cores"
      ],
      "cross_section_mm2": {
        "min": 2.5,
        "max": 500
      },
      "range_type": "declared_continuous_range_not_expanded"
    },
    {
      "profile_id": "4-or-3plus1",
      "core_configurations": [
        "4 cores",
        "3+1 core"
      ],
      "cross_section_mm2": {
        "min": 2.5,
        "max": 500
      },
      "range_type": "declared_continuous_range_not_expanded"
    },
    {
      "profile_id": "5-and-split",
      "core_configurations": [
        "5 cores",
        "3+2 cores",
        "4+1 core"
      ],
      "cross_section_mm2": {
        "min": 50,
        "max": 500
      },
      "range_type": "declared_continuous_range_not_expanded"
    }
  ],
  "construction": {
    "conductor_material": "copper",
    "insulation_material": "pvc",
    "outer_sheath_material": "pvc",
    "screen": {
      "present": false,
      "type": "none"
    },
    "armor": {
      "present": true,
      "type": "steel_tape"
    },
    "conductor_form": "stranded"
  },
  "functions": {
    "flame_retardant": true,
    "flame_retardant_class": [
      "B"
    ],
    "low_smoke_halogen_free": false
  },
  "cross_section_examples": [
    {
      "example_id": "4-core-model-components",
      "basis": "manual_model_table_and_photograph",
      "scope": "illustrated_configuration_with_model_table_materials",
      "model_structure_complete": true,
      "not_to_scale": true,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "cable",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": [
            {
              "kind": "binder"
            },
            {
              "kind": "bedding"
            },
            {
              "kind": "armor",
              "material": "steel_tape"
            },
            {
              "kind": "outer_sheath",
              "material": "pvc"
            }
          ]
        },
        {
          "node_id": "cores",
          "parent_id": "cable",
          "kind": "core",
          "count": 4,
          "layers": [
            {
              "kind": "conductor",
              "material": "copper",
              "form": "stranded"
            },
            {
              "kind": "insulation",
              "material": "pvc"
            }
          ]
        },
        {
          "node_id": "filler",
          "parent_id": "cable",
          "kind": "filler",
          "count": 1,
          "layers": []
        }
      ],
      "illustrated_counts": {
        "cores": 4,
        "groups": 0,
        "tubes": 0,
        "reinforcements": 0
      },
      "note": "Core count follows the shared product photographs or explicit single-core model row. Selected-model materials and armour are kept distinct; colour, dimensions and unlabelled tape materials are not inferred. This does not create an orderable configuration."
    }
  ],
  "technical_details": {
    "minimum_laying_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": 0
    },
    "maximum_conductor_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 70,
      "conditions": "Continuous operation"
    },
    "ambient_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": -15,
      "max": 70
    },
    "short_circuit_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 160,
      "maximum_duration_s": 5
    },
    "system_frequency": {
      "basis": "declared",
      "unit": "Hz",
      "value": 50,
      "supply": "AC"
    },
    "applications": {
      "basis": "declared",
      "values": [
        "Power transmission and distribution; fixed installation in the environments described for the selected construction."
      ]
    },
    "minimum_bending_radius": {
      "basis": "declared",
      "cases": [
        {
          "core_configuration": "1 core",
          "min": 15,
          "unit": "D"
        },
        {
          "core_configuration": "3 cores",
          "min": 12,
          "unit": "D"
        }
      ],
      "diameter_definition": "D is the actual overall cable diameter.",
      "conditions": "Installation; use the case matching the selected core configuration."
    },
    "dimensional_table": {
      "basis": "declared",
      "table_kind": "calculated_continuous_current_reference",
      "reported_row_count": 19,
      "rows": [
        {
          "source_row_id": "pvc-lv-1.5-copper",
          "cross_section_mm2": 1.5,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 26,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 23,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 27,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 24,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 22,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-2.5-copper",
          "cross_section_mm2": 2.5,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 33,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 30,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 35,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 31,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 29,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-4-copper",
          "cross_section_mm2": 4,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 44,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 39,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 46,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 40,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 31,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 38,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-6-copper",
          "cross_section_mm2": 6,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 56,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 49,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 57,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 50,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 38,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 47,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-10-copper",
          "cross_section_mm2": 10,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 77,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 68,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 77,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 68,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 54,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 65,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-16-copper",
          "cross_section_mm2": 16,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 101,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 89,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 98,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 86,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 70,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 84,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-25-copper",
          "cross_section_mm2": 25,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 128,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 113,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 126,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 111,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 91,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 110,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-35-copper",
          "cross_section_mm2": 35,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 161,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 142,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 149,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 131,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 111,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 130,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-50-copper",
          "cross_section_mm2": 50,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 193,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 170,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 181,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 160,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 135,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 155,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-70-copper",
          "cross_section_mm2": 70,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 246,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 216,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 223,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 197,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 170,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 195,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-95-copper",
          "cross_section_mm2": 95,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 299,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 264,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 265,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 234,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 217,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 230,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-120-copper",
          "cross_section_mm2": 120,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 348,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 307,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 302,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 267,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 247,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 260,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-150-copper",
          "cross_section_mm2": 150,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 401,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 353,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 339,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 299,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 288,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 300,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-185-copper",
          "cross_section_mm2": 185,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 460,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 406,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 386,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 340,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 328,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 335,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-240-copper",
          "cross_section_mm2": 240,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 546,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 481,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 446,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 394,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 393,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 390,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-300-copper",
          "cross_section_mm2": 300,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 626,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 552,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 507,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 447,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "current": {
                "reference": 440,
                "unit": "A"
              }
            },
            {
              "core_configuration": "multicore",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "current": {
                "reference": 435,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-400-copper",
          "cross_section_mm2": 400,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 783,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 652,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 581,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 513,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-500-copper",
          "cross_section_mm2": 500,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 856,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 754,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 660,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 582,
                "unit": "A"
              }
            }
          ]
        },
        {
          "source_row_id": "pvc-lv-630-copper",
          "cross_section_mm2": 630,
          "rated_voltage": "0.6/1kV",
          "conductor_material": "copper",
          "maximum_conductor_temperature_c": 70,
          "cases": [
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "flat",
              "current": {
                "reference": 984,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "air",
              "ambient_temperature_c": 40,
              "arrangement": "trefoil",
              "current": {
                "reference": 868,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "flat",
              "current": {
                "reference": 753,
                "unit": "A"
              }
            },
            {
              "core_configuration": "1 core",
              "installation_medium": "soil",
              "ambient_temperature_c": 25,
              "arrangement": "trefoil",
              "current": {
                "reference": 664,
                "unit": "A"
              }
            }
          ]
        }
      ],
      "scope": "Generic cable-class reference table, not an orderable specification. Select the independent product specification first; a reference row does not make its section or core count available.",
      "conditions": "Calculated handbook reference only: air 40 degC or soil 25 degC, with the stated arrangement and conductor temperature. Installation correction factors are not supplied."
    },
    "delivery_conditions": {
      "basis": "declared",
      "normal_minimum_length_m": 100,
      "short_length_m": {
        "less_than": 20
      },
      "maximum_short_length_share_percent": 10,
      "length_tolerance_percent": 0.5,
      "conditions": "The handbook literally permits short pieces below 20 m, totalling at most 10% of delivered length. Other lengths may be agreed. Measurement tolerance is plus or minus 5 per mille (0.5%)."
    }
  },
  "category_ids": [
    "power-cables",
    "low-voltage",
    "flame-retardant",
    "armored"
  ],
  "english_name": "CU/PVC/PVC 0.6/1kV Flame-retardant B Steel Tape Armored Power Cable",
  "english_name_modules": [
    {
      "type": "materials",
      "value": "CU/PVC/PVC"
    },
    {
      "type": "rated_voltage",
      "value": "0.6/1kV"
    },
    {
      "type": "features",
      "value": "Flame-retardant B Steel Tape Armored"
    },
    {
      "type": "product_type",
      "value": "Power Cable"
    }
  ],
  "display_identity": {
    "voltage_class": "LV",
    "qualifiers": [],
    "suffix_origin": "none",
    "notes": [
      "No website suffix is added; the display model preserves the source model."
    ],
    "model_label": "ZB-VV22",
    "title": "ZB-VV22 — Power Cable",
    "enquiry_reference": {
      "source_model": "ZB-VV22",
      "product_id": "xr-lv-pvc-power-0.6-1-zb_vv22",
      "rated_voltage": "0.6/1kV",
      "instruction": "Quote the source model and product_id, together with the required rated voltage, core configuration and cross-section. Website suffixes are reference labels, not manufacturer ordering codes."
    }
  }
}