  "product_id": "xr-b2-power-8.7-15-wdzb2n_yjy",
  "family_id": "b2-power-8.7-15",
  "model": "WDZB2N-YJY",
  "source_notation": "WDZB2N-Y JY",
  "rated_voltage": "8.7/15kV",
  "specification_ranges": [
    {
      "profile_id": "single-core",
      "core_configurations": [
        "1 core"
      ],
      "cross_section_mm2": {
        "min": 25,
        "max": 630
      },
      "range_type": "declared_selectable_range"
    },
    {
      "profile_id": "three-core",
      "core_configurations": [
        "3 cores"
      ],
      "cross_section_mm2": {
        "min": 25,
        "max": 400
      },
      "range_type": "declared_selectable_range"
    }
  ],
  "construction": {
    "conductor_material": "copper",
    "insulation_material": "xlpe",
    "outer_sheath_material": "polyolefin",
    "screen": {
      "present": true,
      "type": "conductor_insulation_and_metal_screen_system",
      "scope": "individual_core",
      "layers": [
        {
          "scope": "individual_core",
          "type": "conductor_screen"
        },
        {
          "scope": "individual_core",
          "type": "insulation_screen"
        },
        {
          "scope": "individual_core",
          "type": "metal_screen"
        }
      ]
    },
    "armor": {
      "present": false,
      "type": "none"
    },
    "conductor_form": "stranded",
    "fire_barrier": "present",
    "oxygen_barrier": {
      "present": true,
      "scope": "overall"
    }
  },
  "functions": {
    "flame_retardant": true,
    "flame_retardant_class": [
      "B2"
    ],
    "fire_resistant": true,
    "low_smoke_halogen_free": true
  },
  "cross_section_examples": [
    {
      "example_id": "three-core-medium-voltage-diagram",
      "basis": "manual_model_table_and_diagram",
      "scope": "model_table_structure_applied_to_illustrated_configuration",
      "not_to_scale": true,
      "model_structure_complete": false,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "cable",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": [
            {
              "kind": "binder",
              "material": "glass_fiber_tape"
            },
            {
              "kind": "separator",
              "function": "oxygen_barrier"
            },
            {
              "kind": "binder",
              "material": "high_flame_retardant_tape"
            },
            {
              "kind": "outer_sheath",
              "material": "polyolefin"
            }
          ]
        },
        {
          "node_id": "cores",
          "parent_id": "cable",
          "kind": "core",
          "count": 3,
          "layers": [
            {
              "kind": "conductor",
              "material": "copper",
              "form": "stranded"
            },
            {
              "kind": "conductor_screen"
            },
            {
              "kind": "insulation",
              "material": "xlpe"
            },
            {
              "kind": "insulation_screen"
            },
            {
              "kind": "metal_screen"
            }
          ]
        },
        {
          "node_id": "filler",
          "parent_id": "cable",
          "kind": "filler",
          "count": 1,
          "layers": [],
          "material": "flame_retardant_filler"
        }
      ],
      "illustrated_counts": {
        "cores": 3,
        "groups": 0,
        "tubes": 0,
        "reinforcements": 0
      },
      "note": "The common drawing does not identify the additional N-variant fire-barrier layer. It is a sourced shared illustration, not a complete N-variant manufacturing recipe."
    }
  ],
  "technical_details": {
    "applications": {
      "basis": "declared",
      "values": [
        "Medium-voltage power distribution"
      ]
    },
    "minimum_laying_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": 0
    },
    "maximum_conductor_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 90,
      "conditions": "Continuous operation"
    },
    "ambient_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": -15,
      "max": 90
    },
    "short_circuit_temperature": {
      "basis": "declared",
      "unit": "degC",
      "max": 250,
      "maximum_duration_s": 5
    },
    "reaction_to_fire_requirements": {
      "basis": "declared",
      "classification": "B2",
      "test_standard": "GB 31247-2014",
      "limits": [
        {
          "parameter": "Flame spread",
          "max": 2.5,
          "unit": "m"
        },
        {
          "parameter": "Peak heat release rate",
          "max": 60,
          "unit": "kW"
        },
        {
          "parameter": "Total heat release",
          "max": 30,
          "unit": "MJ",
          "duration_s": 1200
        },
        {
          "parameter": "Fire growth rate index",
          "max": 300,
          "unit": "W/s"
        },
        {
          "parameter": "Peak smoke production rate",
          "max": 1.5,
          "unit": "m2/s"
        },
        {
          "parameter": "Total smoke production",
          "max": 400,
          "unit": "m2",
          "duration_s": 1200
        },
        {
          "parameter": "Vertical flame spread",
          "max": 425,
          "unit": "mm"
        }
      ],
      "conditions": "Catalogue-declared class requirements; this record is not an individual product test report."
    },
    "handling_guidance": {
      "basis": "declared",
      "values": [
        "Keep drums upright and secure during lifting, transport and storage.",
        "Inspect for damage and check insulation resistance before installation.",
        "Provide allowance for vibration, thermal expansion and building movement."
      ]
    },
    "installation_guidance": {
      "basis": "declared",
      "values": [
        "Avoid twisting, knotting and dragging across sharp or abrasive surfaces.",
        "Fix the cable at bends and on both sides of joints.",
        "Do not use ferromagnetic ties or clamps around single-core cables.",
        "Provide mechanical protection where damage may occur."
      ]
    },
    "minimum_bending_radius": {
      "basis": "declared",
      "cases": [
        {
          "core_configuration": "1 core",
          "min": 20,
          "unit": "D"
        },
        {
          "core_configuration": "Multicore",
          "min": 15,
          "unit": "D"
        }
      ],
      "diameter_definition": "D is the actual overall cable diameter.",
      "conditions": "Installation; use the case matching the selected core configuration."
    },
    "minimum_bending_radius_at_joint": {
      "basis": "declared",
      "cases": [
        {
          "core_configuration": "1 core",
          "min": 15,
          "unit": "D"
        },
        {
          "core_configuration": "Multicore",
          "min": 12,
          "unit": "D"
        }
      ],
      "diameter_definition": "D is the actual overall cable diameter.",
      "conditions": "Careful bending close to a joint or termination, with a forming guide."
    },
    "installation_spacing": {
      "basis": "declared",
      "fixed_point_spacing_mm": [
        {
          "diameter_mm": {
            "less_than": 9
          },
          "horizontal_max": 600,
          "vertical_max": 800
        },
        {
          "diameter_mm": {
            "minimum": 9,
            "less_than": 15
          },
          "horizontal_max": 900,
          "vertical_max": 1200
        },
        {
          "diameter_mm": {
            "minimum": 15
          },
          "horizontal_max": 1500,
          "vertical_max": 2000
        }
      ],
      "support_span_mm": [
        {
          "diameter_mm": {
            "maximum": 20
          },
          "horizontal_max": 400,
          "vertical_max": 1500
        },
        {
          "diameter_mm": {
            "greater_than": 20
          },
          "horizontal_max": 800,
          "vertical_max": 1000
        }
      ],
      "natural_snaking_amplitude": {
        "less_than_outer_diameter_multiple": 2
      },
      "single_core_circuit_separation": {
        "minimum_outer_diameter_multiple": 2,
        "closer_spacing_requires_ampacity_derating": true
      },
      "single_core_fixings_must_be_nonmagnetic": true,
      "conditions": "Handbook installation guidance. D is the cable outer diameter. Fixed-point distances and support spans are distinct tables, not interchangeable limits."
    },
    "movement_allowance_bends": {
      "basis": "declared",
      "shapes": [
        "S",
        "omega"
      ],
      "minimum_radius_outer_diameter_multiple": 15,
      "conditions": [
        "Large ambient temperature changes",
        "Wiring to vibrating equipment",
        "Building settlement or expansion joints",
        "An otherwise entirely straight cable run"
      ]
    }
  },
  "category_ids": [
    "power-cables",
    "medium-voltage",
    "fire-resistant",
    "flame-retardant",
    "b2",
    "lszh",
    "screened"
  ],
  "english_name": "CU/XLPE/Polyolefin 8.7/15kV LSZH Flame-retardant B2 Fire-resistant Screened Power Cable",
  "english_name_modules": [
    {
      "type": "materials",
      "value": "CU/XLPE/Polyolefin"
    },
    {
      "type": "rated_voltage",
      "value": "8.7/15kV"
    },
    {
      "type": "features",
      "value": "LSZH Flame-retardant B2 Fire-resistant Screened"
    },
    {
      "type": "product_type",
      "value": "Power Cable"
    }
  ],
  "display_identity": {
    "voltage_class": "MV",
    "qualifiers": [
      "MV"
    ],
    "suffix_origin": "website_disambiguation",
    "notes": [
      "LV means low voltage; MV means medium voltage. The hyphenated -LV/-MV suffixes are added only where the same source model occurs in distinct voltage classes. They were created for website disambiguation; they are not part of the manufacturer's original model codes.",
      "The voltage-class label is based on the confirmed category_ids and rated_voltage in this record. It does not replace the exact rated voltage or voltage-conditioned specification ranges."
    ],
    "model_label": "WDZB2N-YJY-MV",
    "title": "WDZB2N-YJY-MV — Power Cable",
    "enquiry_reference": {
      "source_model": "WDZB2N-YJY",
      "product_id": "xr-b2-power-8.7-15-wdzb2n_yjy",
      "rated_voltage": "8.7/15kV",
      "instruction": "Quote the source model and product_id, together with the required rated voltage, core configuration and cross-section. Website suffixes are reference labels, not manufacturer ordering codes."
    }
  }
}