  "product_id": "xr-b1-wire-450-750-wdzb1n_rys",
  "family_id": "b1-wire-450-750",
  "model": "WDZB1N-RYS",
  "source_notation": "WDZB1N-RYS",
  "rated_voltage": "300/300V",
  "specification_ranges": [
    {
      "profile_id": "two-core-twisted-wire",
      "core_configurations": [
        "2 cores"
      ],
      "cross_section_mm2": {
        "min": 0.75,
        "max": 6
      },
      "range_type": "declared_selectable_range"
    }
  ],
  "construction": {
    "conductor_material": "copper",
    "insulation_material": "polyolefin",
    "outer_sheath_material": "none",
    "screen": {
      "present": false,
      "type": "none"
    },
    "armor": {
      "present": false,
      "type": "none"
    },
    "conductor_form": "flexible_stranded",
    "stranding": "paired_insulated_cores",
    "fire_barrier": "present"
  },
  "functions": {
    "flame_retardant": true,
    "flame_retardant_class": [
      "B1"
    ],
    "fire_resistant": true,
    "low_smoke_halogen_free": true
  },
  "cross_section_examples": [
    {
      "example_id": "wire-source-configuration",
      "basis": "manual_model_table_and_diagram",
      "scope": "model_table_structure_applied_to_illustrated_configuration",
      "not_to_scale": true,
      "model_structure_complete": true,
      "configuration_is_orderable_specification": false,
      "nodes": [
        {
          "node_id": "cable",
          "parent_id": null,
          "kind": "assembly",
          "count": 1,
          "layers": []
        },
        {
          "node_id": "pair",
          "parent_id": "cable",
          "kind": "group",
          "count": 1,
          "layers": []
        },
        {
          "node_id": "cores",
          "parent_id": "pair",
          "kind": "core",
          "count": 2,
          "layers": [
            {
              "kind": "conductor",
              "material": "copper",
              "form": "flexible_stranded"
            },
            {
              "kind": "fire_barrier"
            },
            {
              "kind": "insulation",
              "material": "polyolefin"
            }
          ]
        }
      ],
      "illustrated_counts": {
        "cores": 2,
        "groups": 1,
        "tubes": 0,
        "reinforcements": 0
      },
      "note": "Source-illustrated core count with the selected model materials. No dimensions, arbitrary combinations or commercial SKU are inferred."
    }
  ],
  "technical_details": {
    "dimensional_table": {
      "basis": "declared",
      "reported_row_count": 6,
      "rows": [
        {
          "source_row_id": "b1-rys-ryjs:2*0.75",
          "composition": [
            {
              "core_count": 2,
              "cross_section_mm2": 0.75
            }
          ],
          "core_count": 2,
          "outer_diameter_mm": 6.9,
          "mass_kg_per_km": 41.2,
          "reference_ampacity": {
            "unit": "A",
            "reference": 12,
            "conditions": "Reference table value only. Installation conditions are not specified in this table; not a universal current rating."
          }
        },
        {
          "source_row_id": "b1-rys-ryjs:2*1",
          "composition": [
            {
              "core_count": 2,
              "cross_section_mm2": 1
            }
          ],
          "core_count": 2,
          "outer_diameter_mm": 7.3,
          "mass_kg_per_km": 47.5,
          "reference_ampacity": {
            "unit": "A",
            "reference": 14,
            "conditions": "Reference table value only. Installation conditions are not specified in this table; not a universal current rating."
          }
        },
        {
          "source_row_id": "b1-rys-ryjs:2*1.5",
          "composition": [
            {
              "core_count": 2,
              "cross_section_mm2": 1.5
            }
          ],
          "core_count": 2,
          "outer_diameter_mm": 7.8,
          "mass_kg_per_km": 58.8,
          "reference_ampacity": {
            "unit": "A",
            "reference": 18,
            "conditions": "Reference table value only. Installation conditions are not specified in this table; not a universal current rating."
          }
        },
        {
          "source_row_id": "b1-rys-ryjs:2*2.5",
          "composition": [
            {
              "core_count": 2,
              "cross_section_mm2": 2.5
            }
          ],
          "core_count": 2,
          "outer_diameter_mm": 8.7,
          "mass_kg_per_km": 82.1,
          "reference_ampacity": {
            "unit": "A",
            "reference": 25,
            "conditions": "Reference table value only. Installation conditions are not specified in this table; not a universal current rating."
          }
        },
        {
          "source_row_id": "b1-rys-ryjs:2*4",
          "composition": [
            {
              "core_count": 2,
              "cross_section_mm2": 4
            }
          ],
          "core_count": 2,
          "outer_diameter_mm": 9.7,
          "mass_kg_per_km": 113.3,
          "reference_ampacity": {
            "unit": "A",
            "reference": 33,
            "conditions": "Reference table value only. Installation conditions are not specified in this table; not a universal current rating."
          }
        },
        {
          "source_row_id": "b1-rys-ryjs:2*6",
          "composition": [
            {
              "core_count": 2,
              "cross_section_mm2": 6
            }
          ],
          "core_count": 2,
          "outer_diameter_mm": 10.9,
          "mass_kg_per_km": 157.3,
          "reference_ampacity": {
            "unit": "A",
            "reference": 42,
            "conditions": "Reference table value only. Installation conditions are not specified in this table; not a universal current rating."
          }
        }
      ],
      "scope": "Original model-specific reference table. Dimensions are approximate and mass is a reference value. These rows do not expand the separately declared selectable ranges."
    },
    "applications": {
      "basis": "declared",
      "values": [
        "Metro stations and transport hubs",
        "Airports",
        "Hospitals",
        "High-rise buildings",
        "Shopping centres, hotels and exhibition centres"
      ],
      "conditions": "Locations requiring the documented B1 reaction-to-fire performance."
    },
    "minimum_laying_temperature": {
      "basis": "declared",
      "unit": "degC",
      "min": 0
    },
    "minimum_bending_radius": {
      "basis": "declared",
      "unit": "D",
      "min": 6,
      "conditions": "Installation",
      "diameter_definition": "D is the actual overall cable diameter."
    },
    "reaction_to_fire_requirements": {
      "basis": "declared",
      "classification": "B1",
      "test_standard": "GB 31247-2014",
      "limits": [
        {
          "parameter": "Flame spread",
          "max": 1.5,
          "unit": "m"
        },
        {
          "parameter": "Peak heat release rate",
          "max": 30,
          "unit": "kW"
        },
        {
          "parameter": "Total heat release",
          "max": 15,
          "unit": "MJ",
          "duration_s": 1200
        },
        {
          "parameter": "Fire growth rate index",
          "max": 150,
          "unit": "W/s"
        },
        {
          "parameter": "Peak smoke production rate",
          "max": 0.25,
          "unit": "m2/s"
        },
        {
          "parameter": "Total smoke production",
          "max": 50,
          "unit": "m2",
          "duration_s": 1200
        },
        {
          "parameter": "Vertical flame spread",
          "max": 425,
          "unit": "mm"
        }
      ],
      "conditions": "Catalogue-declared class requirements; this record is not an individual product test report."
    },
    "handling_guidance": {
      "basis": "declared",
      "values": [
        "Keep drums upright and secure during lifting, transport and storage.",
        "Inspect for damage and check insulation resistance before installation.",
        "Provide allowance for vibration, thermal expansion and building movement."
      ]
    },
    "installation_guidance": {
      "basis": "declared",
      "values": [
        "Avoid twisting, knotting and dragging across sharp or abrasive surfaces.",
        "Fix the cable at bends and on both sides of joints.",
        "Do not use ferromagnetic ties or clamps around single-core cables.",
        "Provide mechanical protection where damage may occur."
      ]
    },
    "maximum_conductor_temperature": {
      "basis": "declared",
      "max": 70,
      "unit": "degC",
      "conditions": "Continuous operation"
    },
    "installation_spacing": {
      "basis": "declared",
      "fixed_point_spacing_mm": [
        {
          "diameter_mm": {
            "less_than": 9
          },
          "horizontal_max": 600,
          "vertical_max": 800
        },
        {
          "diameter_mm": {
            "minimum": 9,
            "less_than": 15
          },
          "horizontal_max": 900,
          "vertical_max": 1200
        },
        {
          "diameter_mm": {
            "minimum": 15
          },
          "horizontal_max": 1500,
          "vertical_max": 2000
        }
      ],
      "support_span_mm": [
        {
          "diameter_mm": {
            "maximum": 20
          },
          "horizontal_max": 400,
          "vertical_max": 1500
        },
        {
          "diameter_mm": {
            "greater_than": 20
          },
          "horizontal_max": 800,
          "vertical_max": 1000
        }
      ],
      "natural_snaking_amplitude": {
        "less_than_outer_diameter_multiple": 2
      },
      "single_core_circuit_separation": {
        "minimum_outer_diameter_multiple": 2,
        "closer_spacing_requires_ampacity_derating": true
      },
      "single_core_fixings_must_be_nonmagnetic": true,
      "conditions": "Handbook installation guidance. D is the cable outer diameter. Fixed-point distances and support spans are distinct tables, not interchangeable limits."
    },
    "conductor_material_declaration": {
      "basis": "declared",
      "copper_purity_percent": 99.99,
      "material_grade": "oxygen_free_copper",
      "conditions": "B1-series manufacturer material declaration in the handbook, not an individual batch assay."
    },
    "movement_allowance_bends": {
      "basis": "declared",
      "shapes": [
        "S",
        "omega"
      ],
      "minimum_radius_outer_diameter_multiple": 15,
      "conditions": [
        "Large ambient temperature changes",
        "Wiring to vibrating equipment",
        "Building settlement or expansion joints",
        "An otherwise entirely straight cable run"
      ]
    }
  },
  "category_ids": [
    "equipment-wires",
    "fire-resistant",
    "flame-retardant",
    "b1",
    "lszh"
  ],
  "english_name": "CU/Polyolefin 300/300V LSZH Flame-retardant B1 Fire-resistant Twisted Pair Equipment Wire",
  "english_name_modules": [
    {
      "type": "materials",
      "value": "CU/Polyolefin"
    },
    {
      "type": "rated_voltage",
      "value": "300/300V"
    },
    {
      "type": "features",
      "value": "LSZH Flame-retardant B1 Fire-resistant Twisted Pair"
    },
    {
      "type": "product_type",
      "value": "Equipment Wire"
    }
  ],
  "display_identity": {
    "voltage_class": null,
    "qualifiers": [],
    "suffix_origin": "none",
    "notes": [
      "No website suffix is added; the display model preserves the source model."
    ],
    "model_label": "WDZB1N-RYS",
    "title": "WDZB1N-RYS — Equipment Wire",
    "enquiry_reference": {
      "source_model": "WDZB1N-RYS",
      "product_id": "xr-b1-wire-450-750-wdzb1n_rys",
      "rated_voltage": "300/300V",